LRD1516: Schneider TeSys LRD Thermal Overload Relays

Image for reference. Refer to the datasheet for exact dimensions.

LRD1516: Schneider TeSys LRD Thermal Overload Relays

Schneider LRD1516, Industrial Applications With Electric Relay. Protect motors—ask IndMALL for pricing today and improve system reliability.

Brand
Schneider
Model number
LRD1516
Series
Schneider Contactors TeSys Deca Overload Relay

Send this enquiry to IndMALL on WhatsApp — the model and page link are filled in. Add the quantity and your company details, and we connect you with the right suppliers.

Schneider LRD1516 technical specifications

Device short nameLRD
RangeTeSys
Product nameTeSys LRDTeSys Deca
[Ith] conventional free air thermal current5 A for signalling circuit
IP degree of protectionIP20 conforming to IEC 60529
Phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0
Temperature compensation-20…60 °C
Auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage6 kV
Thermal overload classClass 20 conforming to IEC 60947-4-1
Network typeDCAC
Tripping threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Control typeRed push-button: stopBlue push-button: reset
Mechanical robustnessVibrations: 6 Gn conforming to IEC 60068-2-6Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
[Ue] rated operational voltage690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
Associated fuse rating4 A gG for signalling circuit4 A BS for signalling circuit
Product certificationsIECULCSAEACDNV-GLLROS (Lloyds register of shipping)UKCA
Permissible current1.5 A at 240 V AC-15 for signalling circuit0.1 A at 250 V DC-13 for signalling circuit
Depth92 mm
Width45 mm
Ambient air temperature for storage-60…70 °C
Climatic withstandconforming to IACS E10
Ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
Dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
Thermal protection adjustment range9…13 A
Flame retardanceV1 conforming to UL 94
Tightening torqueControl circuit: 1.7 N.m - on screw clamp terminalsPower circuit: 1.85 N.m - on screw clamp terminals
Mounting supportPlate, with specific accessoriesRail, with specific accessoriesUnder contactor
Relay applicationMotor protection
Net weight0.19 kg
Specifications as listed by IndMALL. Confirm against the manufacturer's datasheet before ordering.

Overview

Technical Specifications of Schneider TeSys LRD Thermal Overload Relays LRD1516: IndMALL Automation Dealing offers Schneider TeSys LRD Thermal Overload Relays LRD1516 at unbeatable prices. The Main Technical Parameters of LRD1516 are device short name LRD, from the TeSys range. It has a conventional free air thermal current [Ith] of 5 A for signalling circuit, making it suitable for demanding environments. With a height of and an IP20 conforming to IEC 60529, it provides protection against solid objects. The sensor operates efficiently in ambient temperatures ranging from -20…60 °C, with temperature compensation to maintain performance. Choose us for unparalleled pricing and support over other Dealers & Distributors.

Datasheet

Schneider datasheetschneider-electric-lrd1516.pdf

Other models in this series

Compare LRD1516 with similar models in the same series. See all 107 models on the Schneider Contactors TeSys Deca Overload Relay page.

LRD1516 compared with other models in the series
ModelRangeThermal protection adjustment range[Uimp] rated impulse withstand voltageNetwork type
LRD1516 (this model)TeSys9…13 A6 kVDCAC
LRD126TeSysTeSys Deca5.5…8 A6 kVDCAC
LRD1522TeSys17…25 A6 kVACDC
LRD365LTeSysTeSys Deca48…65 A6 kVDCAC
LRD33676TeSys95…120 A6 kVACDC
LRD318TeSysTeSys Deca12…18 A6 kVDCAC
LRD325LTeSysTeSys Deca17…25 A6 kVACDC
LRD21LTeSysTeSys Deca12…18 A6 kVDCAC
LR3D076TeSysTeSys Deca1.6…2.5 A6 kVACDC