IndMALL 2.0 preview — for review only, not indexed by search engines. Links reflect the live IndMALL site; WhatsApp buttons open the real IndMALL enquiry number.

Industrial automation products & suppliers across India

LRD076: Schneider Electric IP20 Industrial Relay For Safety

Image for reference. Refer to the datasheet for exact dimensions.

LRD076: Schneider Electric IP20 Industrial Relay For Safety

Schneider LRD076, IP20 Industrial Relay For Safety. Ensure motor safety—ask IndMALL for pricing today for reliable and efficient motor protection.

Brand
Schneider
Model number
LRD076
Series
Schneider Contactors TeSys Deca Overload Relay

Send this enquiry to IndMALL on WhatsApp — the model and page link are filled in. Add the quantity and your company details, and we connect you with the right suppliers.

Schneider LRD076 technical specifications

Device short nameLRD
RangeTeSysTeSys Deca
Product nameTeSys LRDTeSys Deca
[Ith] conventional free air thermal current5 A for signalling circuit
Height66 mm
IP degree of protectionIP20 conforming to IEC 60529
Phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0
Temperature compensation-20…60 °C
Auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage6 kV
Thermal overload classClass 10A conforming to IEC 60947-4-1
Network typeDCAC
Tripping threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Control typeRed push-button: stopBlue push-button: reset
Mechanical robustnessVibrations: 6 Gn conforming to IEC 60068-2-6Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
[Ue] rated operational voltage690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
Associated fuse rating4 A gG for signalling circuit4 A BS for signalling circuit
Product certificationsIECULCSACCCEACBVRINADNV-GLLROS (Lloyds register of shipping)ATEX INERISUKCA
Permissible current3 A at 120 V AC-15 for signalling circuit0.22 A at 125 V DC-13 for signalling circuit
Depth70 mm
Width45 mm
Ambient air temperature for storage-60…70 °C
Climatic withstandconforming to IACS E10
Ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
Dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
Thermal protection adjustment range1.6…2.5 A
Flame retardanceV1 conforming to UL 94
Tightening torqueControl circuit: 1.7 N.m - on screw clamp terminalsPower circuit: 2.3 N.m - on lugs-ring terminals M4
Mounting supportPlate, with specific accessoriesRail, with specific accessoriesUnder contactor
Relay applicationMotor protection
Net weight0.124 kg
Specifications as listed by IndMALL. Confirm against the manufacturer's datasheet before ordering.

Overview

Technical Specifications of Schneider Electric IP20 Industrial Relay For Safety LRD076: Obtain a Quote for Schneider Electric IP20 Industrial Relay For Safety LRD076 at economical prices. Specifications Overview for LRD076 reveals device short name LRD, from the TeSysTeSys Deca range. It has a conventional free air thermal current [Ith] of 5 A for signalling circuit, making it suitable for demanding environments. With a height of 66 mm and an IP20 conforming to IEC 60529, it provides protection against solid objects. The sensor operates efficiently in ambient temperatures ranging from -20…60 °C, with temperature compensation to maintain performance. The control type consists of a Red push-button: stopBlue push-button: reset.

Datasheet

Schneider datasheetschneider-electric-lrd076.pdf

Other models in this series

Compare LRD076 with similar models in the same series. See all 107 models on the Schneider Contactors TeSys Deca Overload Relay page.

LRD076 compared with other models in the series
ModelRangeThermal protection adjustment range[Uimp] rated impulse withstand voltageNetwork type
LRD076 (this model)TeSysTeSys Deca1.6…2.5 A6 kVDCAC
LR3D3561TeSys55…70 A6 kV conforming to IEC 60947-1ACDC
LR9D5567TeSys60…100 A6 kV conforming to IEC 60947-1AC
LRD05LTeSysTeSys Deca0.63…1 A6 kVDCAC
LRD06L6TeSys1…1.6 A6 kVACDC
LRD07LTeSysTeSys Deca1.6…2.5 A6 kVACDC
LRD07L6TeSysTeSys Deca1.6…2.5 A6 kVACDC
LRD08LTeSysTeSys Deca2.5…4 A6 kVACDC
LRD143TeSysTeSys Deca7…10 A6 kVACDC