Schneider LR3D3561 technical specifications

Device short nameLR3D
RangeTeSys
Product nameTeSys LRDTeSys Deca
[Ith] conventional free air thermal current5 A for signalling circuit
IP degree of protectionIP20 conforming to IEC 60529
Phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0
Temperature compensation-20…60 °C
Auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-1
Thermal overload classClass 20 conforming to IEC 60947-4-1
Network typeACDC
Tripping threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Control typeRed push-button: stopBlue push-button: reset
Mechanical robustnessVibrations: 6 Gn conforming to IEC 60068-2-6Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
[Ue] rated operational voltage690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
Associated fuse rating4 A gG for signalling circuit4 A BS for signalling circuit
Product certificationsIECULCSACCCEACBVDNV-GLLROS (Lloyds register of shipping)UKCA
Depth121 mm
Width75 mm
Ambient air temperature for storage-60…70 °C
Climatic withstandconforming to IACS E10
Ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
Dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
Thermal protection adjustment range55…70 A
Flame retardanceV1 conforming to UL 94
Tightening torqueControl circuit: 1.7 N.m - on screw clamp terminalsPower circuit: 9 N.m - on screw clamp terminals
Mounting supportPlate, with specific accessoriesRail, with specific accessoriesUnder contactor
Relay applicationMotor protection
Net weight0.535 kg
Specifications as listed by IndMALL. Confirm against the manufacturer's datasheet before ordering.

Overview

Here are the brief Technical Specifications of LR3D3561 are device short name LR3D, from the TeSys range. The product, known as TeSys LRDTeSys Deca, is designed for reliable thermal protection in motor control applications. It has a conventional free air thermal current [Ith] of 5 A for signalling circuit, making it suitable for demanding environments. With a height of and an IP20 conforming to IEC 60529, it provides protection against solid objects. The sensor operates efficiently in ambient temperatures ranging from -20…60 °C, with temperature compensation to maintain performance. It supports both ACDC network types. It's Time to get a Quote for your requirement of Schneider Relay With Tripping Sensitivity.

Datasheet

Schneider datasheetschneider-electric-lr3d3561.pdf

Other models in this series

Compare LR3D3561 with similar models in the same series. See all 107 models on the Schneider Contactors TeSys Deca Overload Relay page.

LR3D3561 compared with other models in the series
ModelRangeThermal protection adjustment range[Uimp] rated impulse withstand voltageNetwork type
LR3D3561 (this model)TeSys55…70 A6 kV conforming to IEC 60947-1ACDC
LR3D16TeSysTeSys Deca9…13 A6 kVDCAC
LR3D166TeSysTeSys Deca9…13 A6 kVDCAC
LR3D226TeSysTeSys Deca16…24 A6 kVACDC
LR3D350TeSysTeSys Deca37…50 A6 kVDCAC
LR9D5567TeSys60…100 A6 kV conforming to IEC 60947-1AC
LRD05LTeSysTeSys Deca0.63…1 A6 kVDCAC
LRD06L6TeSys1…1.6 A6 kVACDC
LRD076TeSysTeSys Deca1.6…2.5 A6 kVDCAC