Image for reference. Refer to the datasheet for exact dimensions.
LC1K09004B7: Schneider 20 A 4 NO TeSys K Contactor
Schneider LC1K09004B7, 20A 4 NO TeSys K Contactor. Maximize system control—get a custom quote from IndMALL today and boost your operations.
- Brand
- Schneider
- Model number
- LC1K09004B7
- Series
- Schneider Contactors TeSys K Contactors
Send this enquiry to IndMALL on WhatsApp — the model and page link are filled in. Add the quantity and your company details, and we connect you with the right suppliers.
Schneider LC1K09004B7 technical specifications
| Connections - terminals | Screw clamp terminals 1 cable(s) 1.5…4 mm²solidScrew clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable endScrew clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable endScrew clamp terminals 2 cable(s) 1.5…4 mm²solidScrew clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable endScrew clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end |
|---|---|
| [Uc] control circuit voltage | 24 V AC 50/60 Hz |
| Minimum switching voltage | - |
| contactor application | Resistive load |
| Width | 45 mm |
| Control circuit type | AC at 50/60 Hz |
| Average impedance | 3 mOhm - Ith 20 A 50 Hz for power circuit |
| Depth | 57 mm |
| [Ie] rated operational current | 20 A (at <50 °C) at <= 440 V AC AC-1 for power circuit16 A (at <70 °C) at 690 V AC AC-1 for power circuit |
| Auxiliary contacts type | - |
| poles description | 4P |
| Auxiliary contact composition | - |
| IP degree of protection | IP2X conforming to VDE 0106 |
| [Ui] rated insulation voltage | Power circuit: 600 V conforming to UL 508Power circuit: 690 V conforming to IEC 60947-4-1Power circuit: 600 V conforming to CSA C22.2 No 14 |
| Operating altitude | 2000 m without derating |
| Ambient air temperature for operation | - |
| Power pole contact composition | 4 NO |
| Hold-in power consumption in W | - |
| Ambient air temperature for storage | -50…80 °C |
| Utilisation category | AC-1 |
| Insulation resistance | - |
| Heat dissipation | 1.3 W |
| Hold-in power consumption in VA | 4.5 VA (at 20 °C) |
| Net weight | 0.18 kg |
| Minimum switching current | - |
| Mounting support | PlateRail |
| Operating time | 10...20 ms coil de-energisation and NO opening10...20 ms coil energisation and NO closing |
| Rated breaking capacity | 110 A at 220...230 V conforming to IEC 60947110 A at 380...400 V conforming to IEC 60947110 A at 415 V conforming to IEC 60947110 A at 440 V conforming to IEC 6094780 A at 500 V conforming to IEC 6094770 A at 660...690 V conforming to IEC 60947 |
| Product or component type | Contactor |
| Tightening torque | 0.8…1.3 N.m - on screw clamp terminals Philips No 20.8…1.3 N.m - on screw clamp terminals flat Ø 6 mm |
| Maximum operating rate | 3600 cyc/h |
| Range | TeSys |
| [Ue] rated operational voltage | Power circuit: <= 690 V AC <= 400 HzSignalling circuit: <= 690 V AC <= 400 Hz |
| Height | 58 mm |
| Motor power kW | - |
| Inrush power in W | - |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Electrical durability | 0.16 Mcycles 20 A AC-1 at Ue <= 690 V |
| Device short name | LC1K |
Overview
Technical Specifications of Schneider 20 A 4 NO TeSys K Contactor LC1K09004B7: Please speak to our Technical Engineer for Schneider 20 A 4 NO TeSys K Contactor LC1K09004B7 at attractive prices. Technical Specs Summary of LC1K09004B7 includes control circuit voltage [Uc] operates at 24 V AC 50/60 Hz, with a minimum switching voltage of -, ensuring responsive operation. The control circuit type is AC at 50/60 Hz, and the auxiliary contacts are - configuration, providing reliable switching. The sensor features a 4P design and operates at altitudes up to 2000 m without derating, ensuring versatility across various environments. Heat dissipation 1.3 W, it is energy efficient.
Datasheet
Schneider datasheetschneider-electric-lc1k09004b7.pdfOther models in this series
Compare LC1K09004B7 with similar models in the same series. See all 120 models on the Schneider Contactors TeSys K Contactors page.
| Model | [Uc] control circuit voltage | Minimum switching voltage | Hold-in power consumption in VA | Hold-in power consumption in W |
|---|---|---|---|---|
| LC1K09004B7 (this model) | 24 V AC 50/60 Hz | - | 4.5 VA (at 20 °C) | - |
| LP1K0601ED | 48 V DC | 17 V for signalling circuit | - | 3 W at 20 °C |
| LC1K0610Q7 | 380...400 V AC 50/60 Hz | 17 V for signalling circuit | 4.5 VA (at 20 °C) | - |
| LC1K0610U7 | 230...240 V AC 50/60 Hz | 17 V for signalling circuit | 4.5 VA (at 20 °C) | - |
| LC1K090045B7 | 24 V AC 50/60 Hz | - | 4.5 VA (at 20 °C) | - |
| LC1K09004E7 | 48 V AC 50/60 Hz | - | 4.5 VA (at 20 °C) | - |
| LC1K09004F7 | 110 V AC 50/60 Hz | - | 4.5 VA (at 20 °C) | - |
| LC1K09004P7 | 230 V AC 50/60 Hz | - | 4.5 VA (at 20 °C) | - |
| LC1K09004U7 | 230...240 V AC 50/60 Hz | - | 4.5 VA (at 20 °C) | - |