Image for reference. Refer to the datasheet for exact dimensions.
Schneider ATV6A0C40Q6 Variable Speed Drive
Schneider ATV6A0C40Q6, 690V 400 kW Variable Speed Drive. Optimize performance—contact IndMALL now for pricing and take a operations to the next level
Send this enquiry to IndMALL on WhatsApp — the model and page link are filled in. Add the quantity and your company details, and we connect you with the right suppliers.
Schneider ATV6A0C40Q6 technical specifications
| Degree of protection | UL type 1 conforming to UL 61800-5-1 (cabinet integration)UL type 12 conforming to UL 61800-5-1 (cabinet integration) |
|---|---|
| Supply frequency | 50...60 Hz - 5...5 % |
| Vibration resistance | 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-60.5 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
| IP degree of protection | IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 61800-5-1IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 60529 |
| Speed drive output frequency | 0…500 Hz |
| Electromagnetic compatibility | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-41.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
| Product or component type | Variable speed drive |
| Output voltage | <= power supply voltage |
| Asynchronous motor control profile | Constant torque standardVariable torque standardOptimized torque mode |
| Mounting mode | Cabinet mount |
| Ambient air temperature for storage | -40…70 °C |
| Continuous output current | 425.0 A at 2.5 kHz normal duty340.0 A at 2.5 kHz heavy duty |
| Relay output type | - |
| Minimum switching current | - |
| Electrical connection | Control: removable screw terminals 0.5...1.5 mm²/AWG 20...AWG 16Line side: screw terminalMotor: M10 x 2 bars |
| Synchronous motor control profile | Permanent magnet motorSynchronous reluctance motor |
| Physical interface | 2-wire RS 485 for Modbus serial |
| Pollution degree | 2 conforming to IEC 61800-5-1 |
| Type of polarization | No impedance for Modbus serial |
| Product destination | Synchronous motorsAsynchronous motors |
| Number of preset speeds | 16 preset speeds |
| Operating altitude | < 2000 m with current derating above 1000m |
| Apparent power | 471 kVA at 690 V normal duty378 kVA at 690 V heavy duty |
| [Us] rated supply voltage | 690 V - 15...10 % |
| Ambient air temperature for operation | -10…40 °C without derating40…50 °C with derating factor |
| Supply | - |
| Switching frequency | 2...4.9 kHz adjustable with derating factor |
| Motor power kW | 400.0 kW at 690 V normal duty315.0 kW at 690 V heavy duty |
| EMC filter | Integrated with 300 m conforming to IEC 61800-3 category C3 |
| Communication port protocol | EthernetModbus serialModbus TCP |
| Analogue input type | - |
| Maximum switching current | - |
| Range of product | Altivar Process ATV600 |
| Shock resistance | 4 gn for 11 ms conforming to IEC 60068-2-27 |
| Power dissipation in W | Forced convection: 7180 W, switching frequency 2.5 kHz (normal duty)Forced convection: 5560 W, switching frequency 2.5 kHz (heavy duty) |
| Nominal switching frequency | 2.5 kHz |
| Motor power hp | - |
| Network number of phases | 3 phases |
Overview
The Schneider ATV6A0C40Q6 Variable Speed Drive offers a 400.0 kW at 690 V normal duty315.0 kW at 690 V heavy duty motor power, 2-wire RS 485 for Modbus serial , 3 phases . The Main Technical Parameters of ATV6A0C40Q6 are Altivar Process ATV600 range, with top-notch specifications. The supply frequency is 50...60 Hz - 5...5 %, while the speed drive output frequency ranges from 0…500 Hz, ensuring flexibility in applications. It features a 2-wire RS 485 for Modbus serial physical interface communication, supporting efficient data transfer. The sensor operates at altitudes below < 2000 m with current derating above 1000m.
Datasheet
Schneider datasheetschneider-electric-atv6a0c40q6.pdfOther models in this series
Compare ATV6A0C40Q6 with similar models in the same series. See all 106 models on the Altivar ATV600 page.
| Model | Range of product | [Us] rated supply voltage | Minimum switching current | Communication port protocol |
|---|---|---|---|---|
| ATV6A0C40Q6 (this model) | Altivar Process ATV600 | 690 V - 15...10 % | - | EthernetModbus serialModbus TCP |
| ATV6A0C35R4 | Altivar Process ATV600 | 440 V - 15...10 % | Relay output R1, R2, R3: 5 mA at 24 V DC | EthernetModbus serialModbus TCP |
| ATV6A0C35T4 | Altivar Process ATV600 | 480 V - 15...10 % | Relay output R1, R2, R3: 5 mA at 24 V DC | EthernetModbus serialModbus TCP |
| ATV6A0C40N6 | Altivar Process ATV600 | 500 V - 10...15 % | - | EthernetModbus serialModbus TCP |
| ATV6A0C40Q4 | Altivar Process ATV600 | 400 V - 15...10 % | Relay output R1, R2, R3: 5 mA at 24 V DC | EthernetModbus serialModbus TCP |
| ATV6A0C40R4 | Altivar Process ATV600 | 440 V - 15...10 % | Relay output R1, R2, R3: 5 mA at 24 V DC | EthernetModbus serialModbus TCP |
| ATV6A0C40T4 | Altivar Process ATV600 | 480 V - 15...10 % | Relay output R1, R2, R3: 5 mA at 24 V DC | EthernetModbus serialModbus TCP |
| ATV6A0C40T6 | Altivar Process ATV600 | 600 V - 15...10 % | - | EthernetModbus serialModbus TCP |
| ATV6A0C45Q4 | Altivar Process ATV600 | 400 V - 15...10 % | Relay output R1, R2, R3: 5 mA at 24 V DC | EthernetModbus serialModbus TCP |