IndMALL 2.0 preview — for review only, not indexed by search engines. Links reflect the live IndMALL site; WhatsApp buttons open the real IndMALL enquiry number.

Industrial automation products & suppliers across India

Omron H3Y-4-B AC200-230 10S Solid-state Timer

Image for reference. Refer to the datasheet for exact dimensions.

Omron H3Y-4-B AC200-230 10S Solid-state Timer

Omron H3Y-4-B AC200-230 10S Timer, Power ON-delay type, 4PDT time-limit output, 100–120 VAC, 85–110% range, 10% reset, IP40, 8-pin socket, solid-state H3Y Series.

Brand
Omron
Model number
H3Y-4-B AC200-230 10S
Series
H3Y Series
Product type
Timers

Send this enquiry to IndMALL on WhatsApp — the model and page link are filled in. Add the quantity and your company details, and we connect you with the right suppliers.

Omron H3Y-4-B AC200-230 10S technical specifications

Rated power supply voltage200 to 230 VAC 50/60 Hz
Allowable voltage variable range85 to 110% of the power supply voltage
Reset voltage10% min, of rated supply voltage
Number of time ranges1
Operation modePower ON-delay
Control output (Type)Time-limit: 4PDT
Control output (Contact output)Resistive load: 3 A at 250 VAC (cosφ=1) Minimum applicable load: 1 mA at 1 VDC (failure level: P)
Operating resettingTime-limit operation/Self-reset
Connection method14-pin round socket (Push-In Plus Terminal Block)
Power consumptionApprox. 1.8 VA (at 230 VAC)
Ambient temperature rangeOperating: -10 to 55 ℃ (with no icing) Storage: -25 to 65 ℃ (with no icing)
Accuracy of operating time±1% FS max.
Setting error±10% FS ±50 ms max.
Influence of voltage±2% FS ±10 ms max.
Influence of temperature±2% FS ±10 ms max.
Insulation resistance100 MΩ min. (at 500 VDC)
Dielectric strengthBetween current carrying terminals and exposed non-current carrying metal parts: 2000 VAC 50/60 Hz 1 min (Terminal screw sections are not excluded) Between operating power circuit and control output: 2,000 VAC 50/60 Hz 1 min Between contacts of different polarity: 1,500 VAC 50/60 Hz 1 min Between non-continuous contacts: 1,000 VAC 50/60 Hz 1 min
Impulse withstand voltageBetween power terminals: 3 kV Between current carrying terminals and exposed non-current carrying metal parts: 4.5 kV
Noise immunity±1.5 kV square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise)
Static immunityMulfunction: 4 kV, Destruction: 8 kV
Vibration resistanceDestruction: 10 to 55 Hz, 0.75 mm single amplitude each in 3 directions for 1 hour Malfunction: 10 to 55 Hz, 0.5 mm single amplitude each in 3 directions for 10 min
Shock resistanceDestruction: 1,000 m/s2, 3 times each in 6 directions Malfunction: 100 m/s2, 3 times each in 6 directions
Degree of protectionIP40
Case colorBlack
Ambient temperature rangeOperating: -10 to 55 ℃ (with no icing) Storage: -25 to 65 ℃ (with no icing)
Ambient humidity rangeOperating: 35 to 85%
Reset time0.1 s max. (including halfway reset)
Life expectancy (relay output)Electrical: 200,000 operations min. (3 A at 250 VAC, resistive load at 1800 operations/h, Room temperature) Mechanical: 10 million operations min. (under no load at 1,800 operations/h)
WeightApprox. 50 g
Specifications as listed by IndMALL. Confirm against the manufacturer's datasheet before ordering.

Overview

The Omron H3Y-4-B AC200-230 10S Timer is a solid-state timer designed for precise Power Power ON-delay operation within 1 time range. It supports an allowable voltage variable range of 85 to 110% of the power supply voltage voltage, ensuring stable performance in standard applications. The required reset voltage is 10% min, of rated supply voltage, supporting dependable reset behavior. This timer provides a 4PDT time-limit control output, an IP40 degree of protection, and an 14-pin round socket (Push-In Plus Terminal Block). Manufactured by Omron , listed under Omron Timers , and part of the Omron H3Y-4 Series .

Datasheet

Omron datasheeth3y-datasheet.pdf

Other models in this series

Compare H3Y-4-B AC200-230 10S with similar models in the same series. See all 78 models on the H3Y Series page.

H3Y-4-B AC200-230 10S compared with other models in the series
ModelAllowable voltage variable rangePower consumptionAccuracy of operating time
H3Y-4-B AC200-230 10S (this model)85 to 110% of the power supply voltageApprox. 1.8 VA (at 230 VAC)±1% FS max.
H3Y-4-B AC100-120 30M85 to 110% of the power supply voltageApprox. 1.5 VA (at 120 VAC)±1% FS max.
H3Y-4-B AC100-120 60M85 to 110% of the power supply voltageApprox. 1.5 VA (at 120 VAC)±1% FS max.
H3Y-4-B AC200-230 0.5S85 to 110% of the power supply voltageApprox. 1.8 VA (at 230 VAC)±1% FS ±10 ms max.
H3Y-4-B AC200-230 10M85 to 110% of the power supply voltageApprox. 1.8 VA (at 230 VAC)±1% FS max.
H3Y-4-B AC200-230 30M85 to 110% of the power supply voltageApprox. 1.8 VA (at 230 VAC)±1% FS max.
H3Y-4-B DC100-110 10S85 to 110% of the power supply voltageApprox. 1.3 W (at 110 VDC)±1% FS max.
H3Y-4-B DC100-110 120S85 to 110% of the power supply voltageApprox. 1.3 W (at 110 VDC)±1% FS max.
H3Y-4-B DC12 30S90 to 110% of the power supply voltageApprox. 0.9 W (at 12 VDC)±1% FS max.